Voltage
Time
HystAbs1
PICKUP
TRIP
PICKUP
Pickup1
PICKUP
TRIP
t
tIReset1
Time
Time
Integrator
t
Frozen Timer
Linearly decreased
Instantaneous
Measured
Voltage
ANSI05000020‐3‐en.vsdx
ANSI05000020 V3 EN-US
Figure 341: Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay
Definite timer delay
When definite time delay is selected, the function will trip as shown in figure 342. Detailed
information about individual stage reset/operation behavior is shown in figure 343 and figure 344
respectively. Note that by setting
tResetn
=
0.0s
, instantaneous reset of the definite time delayed
stage is ensured.
Section 9 1MRK 502 066-UUS B
Voltage protection
632
Technical manual