Name Type Description
PU_DI_A BOOLEAN Pickupof sudden change in current, phase A
PU_DI_B BOOLEAN Start signal of sudden change in current, phase B
PU_DI_C BOOLEAN Start signal of sudden change in current, phase C
PU_DV BOOLEAN Common start signal of sudden change in voltage
PU_DV_A BOOLEAN Start signal of sudden change in voltage, phase A
PU_DV_B BOOLEAN Start signal of sudden change in voltage, phase B
PU_DV_C BOOLEAN Start signal of sudden change in voltage, phase C
13.2.5 Settings
PID-3492-SETTINGS v7
Table 429: FUFSPVC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OpModeSel Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
- - V0I0 Operating mode selection
3V0PU 1 - 100 %VB 1 30 Pickup of residual overvoltage element in
% of VBase
3I0PU 1 - 100 %IB 1 10 Pickup of residual undercurrent element in
% of IBase
3V2PU 1 - 100 %VB 1 30 Pickup of negative sequence overvoltage
element in % of VBase
3I2PU 1 - 100 %IB 1 10 Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI Disabled
Enabled
- - Disabled Operation of change based function
Disable/Enable
DVPU 1 - 100 %VB 1 60 Pickup of change in phase voltage in % of
VBase
DIPU 1 - 100 %IB 1 15 Pickup of change in phase current in % of
IBase
VPPU 1 - 100 %VB 1 70 Pickup of phase voltage in % of VBase
IPPU 1 - 100 %IB 1 10 Pickup of phase current in % of IBase
SealIn Disabled
Enabled
- - Enabled Seal in functionality Disable/Enable
VSealInPU 1 - 100 %VB 1 70 Pickup of seal-in phase voltage in % of
VBase
IDLDPU 1 - 100 %IB 1 5 Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU 1 - 100 %VB 1 60 Pickup for phase voltage detection in % of
VBase for dead line detection
Section 13 1MRK 502 066-UUS B
Secondary system supervision
732