VP152
VP489G
VP389G
VPS2289G
389G_OP
152_OP
489G_OP
EXDU_89G
VPS2289G
S2289G_OP
289_EX1
VP489G
S2289G_CL
489G_CL
189_OP
289_OP
189_OP
152_OP
289_CL
VP289
289_OP
VP189
189_CL
189_OP
VP289
VP189
VP152
289ITL
289REL
en04000543_ansi.vsd
EXDU_89G
289_EX2
VP189
VP289
389GREL
389GITL
289_OP
S1S2CLTR
289OPTR
489GREL
489GITL
189OPTR
189CLTR
VP189TR
289CLTR
VP289TR
S1S2OPTR
VPS1S2TR
AND
OR
NOT
NOT
NOT
NOT
AND
AND
AND
OR
ANSI04000543 V1 EN-US
14.2.5.5 Signals
PID-3498-INPUTSIGNALS v4
Table 452: A1A2_BS (3) Input signals
Name Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
189_OP BOOLEAN 0 189 is in open position
189_CL BOOLEAN 0 189 is in closed position
289_OP BOOLEAN 0 289 is in open position
289_CL BOOLEAN 0 289 is in closed position
389G_OP BOOLEAN 0 389G is in open position
389G_CL BOOLEAN 0 389G is in closed position
489G_OP BOOLEAN 0 489G is in open position
489G_CL BOOLEAN 0 489G is in closed position
S189G_OP BOOLEAN 0 S189G on bus section 1 is in open position
S189G_CL BOOLEAN 0 S189G on bus section 1 is in closed position
S289G_OP BOOLEAN 0 S289G on bus section 2 is in open position
S289G_CL BOOLEAN 0 S289G on bus section 2 is in closed position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
Table continues on next page