Name Type Default Description
989_EX3 BOOLEAN 0 External condition for apparatus 989
989_EX4 BOOLEAN 0 External condition for apparatus 989
989_EX5 BOOLEAN 0 External condition for apparatus 989
989_EX6 BOOLEAN 0 External condition for apparatus 989
989_EX7 BOOLEAN 0 External condition for apparatus 989
PID-3593-OUTPUTSIGNALS v5
Table 459: BH_LINE_A (3) Output signals
Name Type Description
152CLREL BOOLEAN Closing of 152 is allowed
152CLITL BOOLEAN Closing of 152 is not allowed
689REL BOOLEAN Switching of 689 is allowed
689ITL BOOLEAN Switching of 689 is not allowed
189REL BOOLEAN Switching of 189 is allowed
189ITL BOOLEAN Switching of 189 is not allowed
189GREL BOOLEAN Switching of 189G is allowed
189GITL BOOLEAN Switching of 189G is not allowed
289GREL BOOLEAN Switching of 289G is allowed
289GITL BOOLEAN Switching of 289G is not allowed
389GREL BOOLEAN Switching of 389G is allowed
389GITL BOOLEAN Switching of 389G is not allowed
989REL BOOLEAN Switching of 989 is allowed
989ITL BOOLEAN Switching of 989 is not allowed
989GREL BOOLEAN Switching of 989G is allowed
989GITL BOOLEAN Switching of 989G is not allowed
189OPTR BOOLEAN 189 is in open position
189CLTR BOOLEAN 189 is in closed position
VP189TR BOOLEAN Switch status of 189 is valid (open or closed)
PID-3594-INPUTSIGNALS v5
Table 460: BH_LINE_B (3) Input signals
Name Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
689_OP BOOLEAN 0 689 is in open position
689_CL BOOLEAN 0 689 is in closed position
289_OP BOOLEAN 0 289 is in open position
289_CL BOOLEAN 0 289 is in closed position
Table continues on next page
1MRK 502 066-UUS B Section 14
Control
795
Technical manual