Name Type Default Description
6189_EX1 BOOLEAN 0 External condition for apparatus 6189
6189_EX2 BOOLEAN 0 External condition for apparatus 6189
6289_EX1 BOOLEAN 0 External condition for apparatus 6289
6289_EX2 BOOLEAN 0 External condition for apparatus 6289
PID-3501-OUTPUTSIGNALS v5
Table 463: BH_CONN (3) Output signals
Name Type Description
152CLREL BOOLEAN Closing of 152 is allowed
152CLITL BOOLEAN Closing of 152 is not allowed
6189REL BOOLEAN Switching of 6189 is allowed
6189ITL BOOLEAN Switching of 6189 is not allowed
6289REL BOOLEAN Switching of 6289 is allowed
6289ITL BOOLEAN Switching of 6289 is not allowed
189GREL BOOLEAN Switching of 189G is allowed
189GITL BOOLEAN Switching of 189G is not allowed
289GREL BOOLEAN Switching of 289G is allowed
289GITL BOOLEAN Switching of 289G is not allowed
14.2.9 Interlocking for double CB bay DB (3)
IP14167-1 v2
14.2.9.1 Identification
GUID-D6D10255-2818-44E4-A44E-DF623161C486 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for double CB bay DB_BUS_A - 3
Interlocking for double CB bay DB_BUS_B - 3
Interlocking for double CB bay DB_LINE - 3
14.2.9.2 Functionality
M13585-3 v10
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A (3), DB_BUS_B
(3) and DB_LINE (3) functions are used for a line connected to a double busbar arrangement
according to figure
423.
Section 14 1MRK 502 066-UUS B
Control
798
Technical manual