M13596-3 v6
ANSI05000355-2-en.vsd
DB_BUS_B (3)
252_OP
252_CL
289_OP
289_CL
6289_OP
6289_CL
489G_OP
489G_CL
589G_OP
589G_CL
389G_OP
389G_CL
2189G_OP
2189G_CL
EXDU_89G
6289_EX1
6289_EX2
289_EX1
289_EX2
252CLREL
252CLITL
6289REL
6289ITL
289REL
289ITL
489GREL
489GITL
589GREL
589GITL
289OPTR
289CLTR
VP289TR
ANSI05000355 V2 EN-US
Figure 426: DB_BUS_B (3) function block
14.2.9.5 Signals
PID-3598-INPUTSIGNALS v5
Table 464: DB_BUS_A (3) Input signals
Name Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
189_OP BOOLEAN 0 189 is in open position
189_CL BOOLEAN 0 189 is in closed position
6189_OP BOOLEAN 0 6189 is in open position
6189_CL BOOLEAN 0 6189 is in closed position
189G_OP BOOLEAN 0 189G is in open position
189G_CL BOOLEAN 0 189G is in closed position
289G_OP BOOLEAN 0 289G is in open position
289G_CL BOOLEAN 0 289G is in closed position
389G_OP BOOLEAN 0 389G is in open position
389G_CL BOOLEAN 0 389G is in closed position
1189G_OP BOOLEAN 0 Grounding switch 1189G on busbar 1 is in open position
1189G_CL BOOLEAN 0 Grounding switch 1189G on busbar 1 is in closed position
EXDU_89G BOOLEAN 0 No transm error from bay containing grounding switch 1189G
6189_EX1 BOOLEAN 0 External condition for apparatus 6189
6189_EX2 BOOLEAN 0 External condition for apparatus 6189
189_EX1 BOOLEAN 0 External condition for apparatus 189
189_EX2 BOOLEAN 0 External condition for apparatus 189
1MRK 502 066-UUS B Section 14
Control
805
Technical manual