PID-3601-OUTPUTSIGNALS v5
Table 467: DB_BUS_B (3) Output signals
Name Type Description
252CLREL BOOLEAN Closing of 252 is allowed
252CLITL BOOLEAN Closing of 252 is not allowed
6289REL BOOLEAN Switching of 6289 is allowed
6289ITL BOOLEAN Switching of 6289 is not allowed
289REL BOOLEAN Switching of 289 is allowed
289ITL BOOLEAN Switching of 289 is not allowed
489GREL BOOLEAN Switching of 489G is allowed
489GITL BOOLEAN Switching of 489G is not allowed
589GREL BOOLEAN Switching of 589G is allowed
589GITL BOOLEAN Switching of 589G is not allowed
289OPTR BOOLEAN 289 is in open position
289CLTR BOOLEAN 289 is in closed position
VP289TR BOOLEAN Switch status of 289 is valid (open or closed)
PID-3508-INPUTSIGNALS v6
Table 468: DB_LINE (3) Input signals
Name Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
252_OP BOOLEAN 0 252 is in open position
252_CL BOOLEAN 0 252 is in closed position
6189_OP BOOLEAN 0 6189 is in open position
6189_CL BOOLEAN 0 6189 is in closed position
189G_OP BOOLEAN 0 189G is in open position
189G_CL BOOLEAN 0 189G is in closed position
289G_OP BOOLEAN 0 289G is in open position
289G_CL BOOLEAN 0 289G is in closed position
6289_OP BOOLEAN 0 6289 is in open position
6289_CL BOOLEAN 0 6289 is in closed position
489G_OP BOOLEAN 0 489G is in open position
489G_CL BOOLEAN 0 489G is in closed position
589G_OP BOOLEAN 0 589G is in open position
589G_CL BOOLEAN 0 589G is in closed position
989_OP BOOLEAN 0 989 is in open position
989_CL BOOLEAN 0 989 is in closed position
389G_OP BOOLEAN 0 389G is in open position
389G_CL BOOLEAN 0 389G is in closed position
Table continues on next page
1MRK 502 066-UUS B Section 14
Control
807