Name Type Default Description
2189G_CL BOOLEAN 0 Grounding switch 2189G on busbar 2 is in closed position
7189G_OP BOOLEAN 0 Grounding switch 7189G on busbar 7 is in open position
7189G_CL BOOLEAN 0 Grounding switch 7189G on busbar 7 is in closed position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar bus7 except in the own bay are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar Bus1 and Bus2
BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar 1 and Bus 7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar Bus1 and Bus7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar 2 and Bus 7
BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar Bus2 and Bus7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar WA7 are valid
VP_BC_12 BOOLEAN 0 Status of the bus coupler apparatuses between Bus1 and Bus2 are
valid
VP_BC_17 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA7 are valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler app. between WA2 and WA7 are valid
EXDU_89G BOOLEAN 0 No transm error from any bay containing grounding switches
EXDU_BPB BOOLEAN 0 No transm error from any bay with disconnectors on WA7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
989_EX1 BOOLEAN 0 External condition for apparatus 989
989_EX2 BOOLEAN 0 External condition for apparatus 989
189_EX1 BOOLEAN 0 External condition for apparatus 189
189_EX2 BOOLEAN 0 External condition for apparatus 189
189_EX3 BOOLEAN 0 External condition for apparatus 189
289_EX1 BOOLEAN 0 External condition for apparatus 289
289_EX2 BOOLEAN 0 External condition for apparatus 289
289_EX3 BOOLEAN 0 External condition for apparatus 289
789_EX1 BOOLEAN 0 External condition for apparatus 789
789_EX2 BOOLEAN 0 External condition for apparatus 789
789_EX3 BOOLEAN 0 External condition for apparatus 789
789_EX4 BOOLEAN 0 External condition for apparatus 789
PID-3509-OUTPUTSIGNALS v5
Table 471: ABC_LINE (3) Output signals
Name
Type Description
152CLREL BOOLEAN Closing of 152 is allowed
152CLITL BOOLEAN Closing of 152 is not allowed
989REL BOOLEAN Switching of 989 is allowed
989ITL BOOLEAN Switching of 989 is not allowed
Table continues on next page
1MRK 502 066-UUS B Section 14
Control
817
Technical manual