Name Type Description
189GITL BOOLEAN Switching of 189G is not allowed
289GREL BOOLEAN Switching of 289G is allowed
289GITL BOOLEAN Switching of 289G is not allowed
189OPTR BOOLEAN 189 is in open position
189CLTR BOOLEAN 189 is in closed position
289OPTR BOOLEAN 289 is in open position
289CLTR BOOLEAN 289 is in closed position
1289OPTR BOOLEAN 189 or 289 or both are in open position
1289CLTR BOOLEAN 189 and 289 are not in open position
VP189TR BOOLEAN Switch status of 189 is valid (open or closed)
VP289TR BOOLEAN Switch status of 289 is valid (open or closed)
VP1289TR BOOLEAN Switch status of 189 and 289 are valid (open or closed)
14.2.12 Position evaluation POS_EVAL
GUID-F20A8939-E91E-44F6-920C-083E5D3FCDFD v2
14.2.12.1 Identification
GUID-3C4B9379-C861-406C-9295-0309014D548E v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Position evaluation POS_EVAL - -
14.2.12.2 Functionality
GUID-C3D07B40-FF01-45C5-A083-EED5643A5FCC v4
Position evaluation (POS_EVAL) function converts the input position data signal POSITION,
consisting of value, time and signal status, to binary signals OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
14.2.12.3 Function block
GUID-B5EF4A28-9C9F-4558-8CD6-453FB480314B v2
POS_EVAL
POSITION OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN-US
Figure 431: POS_EVAL function block
Section 14 1MRK 502 066-UUS B
Control
824
Technical manual