Cause
number
Name Description Supported
14 1-of-n-control Control action is blocked because another control action in a
domain (for example, substation) is already running (in any
XCBR or XSWI of that domain, the DPC.stSeld=”TRUE”)
X
15 Abortion-by-cancel Control action is aborted due to cancel service X
16 Time-limit-over Control action is terminated due to exceed of some time limit X
17 Abortion-by-trip Control action is aborted due to a trip (PTRC with
ACT.general=”TRUE”)
X
18 Object-not-selected Control action is rejected, because control object was not
selected
X
19 Object-already-
selected
Select action is not executed because the addressed object is
already selected
X
20 No-access-authority Control action is blocked due to lack of access authority X
21 Ended-with-overshoot Control action executed but the end position has overshoot
22 Abortion-due-to-
deviation
Control action is aborted due to deviation between the
command value and the measured value
23 Abortion-by-
communication-loss
Control action is aborted due to the loss of connection with
the client that issued the control
24 Blocked-by-command Control action is blocked due to the data attribute
CmdBlk.stVal is TRUE
X
26 Inconsistent-
parameters
The parameters between successive control services are not
consistent, for example the ctlNum of Select and Operate
service are different
X
27 Locked-by-other-client Another client has already reserved the object X
-22 Wrong-Ctl-model Command from client uses wrong control model X
-23 Blocked-by-command Blocked by command X
-24 Blocked-for-open-cmd Blocked for Open command X
-25 Blocked-for-close-cmd Blocked for Close Command X
-30 Long-operation-time Operation time too long X
-31 Switch-not-start-
moving
Switch did not start moving X
-32 Persistent-
intermediate-state
Switch stopped in intermediate state X
-33 Switch-returned-to-
init-pos
Switch returned to the initial position X
-34 Switch-in-bad-state Switch is in a bad position state X
-35 Not-expected-final-
position
Switch did not reach the expected final position X
Section 14 1MRK 502 066-UUS B
Control
828
Technical manual