Name Type Description
HMICTR4 INTEGER Bitmask output 4 to local remote LHMI input
HMICTR5 INTEGER Bitmask output 5 to local remote LHMI input
HMICTR6 INTEGER Bitmask output 6 to local remote LHMI input
HMICTR7 INTEGER Bitmask output 7 to local remote LHMI input
HMICTR8 INTEGER Bitmask output 8 to local remote LHMI input
HMICTR9 INTEGER Bitmask output 9 to local remote LHMI input
HMICTR10 INTEGER Bitmask output 10 to local remote LHMI input
HMICTR11 INTEGER Bitmask output 11 to local remote LHMI input
HMICTR12 INTEGER Bitmask output 12 to local remote LHMI input
14.3.5.3 Settings
PID-3944-SETTINGS v4
Table 487: LOCREM Non group settings (basic)
Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch
External LR-
switch
- - Internal LR-
switch
Control mode for internal/external LR-
switch
PID-3943-SETTINGS v1
14.3.5.4 Operation principle
M17087-3 v7
The function block Local remote (LOCREM) handles the signals coming from the local/remote
switch. The connections are seen in Figure 435, where the inputs on function block LOCREM are
connected to binary inputs if an external switch is used. When the local HMI is used, the inputs are
not used. The switching between external and local HMI source is done through the parameter
ControlMode
. The outputs from the LOCREM function block control the output PSTO (Permitted
Source To Operate) on Bay control (QCBAY).
1MRK 502 066-UUS B Section 14
Control
835
Technical manual