14.3.6.2 Function block
M13482-3 v5
SCSWI
BL OCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_GRT
RES_EXT
SY_INPRO
S YNC_OK
EN_OPEN
EN_CLOSE
XPOSL1*
XPOSL2*
XPOSL3*
EXE_OP
EXE_CL
S EL_OP
S EL_CL
SELECTED
RES_RQ
STAR T_SY
CANC_SY
POSITION
OPENP OS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUS E
POS_INTR
XEXINF
IEC05000337-6-en.vsdx
IEC05000337 V6 EN-US
Figure 436: SCSWI function block
14.3.6.3 Signals
PID-6500-INPUTSIGNALS v3
Table 488: SCSWI Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
L_SEL BOOLEAN 0 Select signal from local panel
L_OPEN BOOLEAN 0 Open signal from local panel
L_CLOSE BOOLEAN 0 Close signal from local panel
AU_OPEN BOOLEAN 0 Used for local automation function
AU_CLOSE BOOLEAN 0 Used for local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted by the synchronism-check
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOSL1 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase
XPOSL2 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase
XPOSL3 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase