14.3.6.4 Settings
PID-6500-SETTINGS v3
Table 490: SCSWI Non group settings (basic)
Name Values (Range) Unit Step Default Description
CtlModel Dir Norm
SBO Enh
- - SBO Enh Specifies control model type
PosDependent Always permitted
Not perm at
00/11
- - Always
permitted
Permission to operate depending on the
position
tSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select and
execute signals
tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request to
reservation granted
tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchronism-check to
fulfil close conditions
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command execution
to termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy between
the poles
SuppressMidPos Disabled
Enabled
- - Enabled Mid-position is suppressed during the
time tIntermediate
InterlockChk Sel & Op phase
Op phase
- - Sel & Op phase Selection if interlock check should be done
in select phase
14.3.6.5 Operation principle
M13484-4 v4
The Switch controller (SCSWI) is provided with verification checks for the select - execute
sequence, that is, checks the conditions prior each step of the operation are fulfilled. The involved
functions for these condition verifications are interlocking, reservation, blockings and
synchronism-check.
Control handling
M13484-6 v6
.
Two types of control models can be used. The two control models are "direct with normal security"
and "SBO (Select-Before-Operate) with enhanced security". The parameter
CtlModel
defines which
one of the two control models is used. The control model "direct with normal security" does not
require a select whereas, the "SBO with enhanced security" command model requires a select
before execution. The command sequence for a command with control mode SBO with enhanced
security is shown in figure
437, with control mode direct with normal security is shown in figure
438.
1MRK 502 066-UUS B Section 14
Control
839