PID-6800-OUTPUTSIGNALS v4
Table 495: SXSWI Output signals
Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm, 2=Warning,
3=Alarm
SWOPCAP INTEGER Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C
14.3.8.4 Settings
PID-6800-SETTINGS v4
Table 496: SXSWI Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end
position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
- - Disconnector Load Break, Disconnector, Grounding
Switch, HS Grounding. Switch
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial count
value)
14.3.8.5 Operation principle
M16494-3 v6
The users of the Circuit switch (SXSWI) are other functions such as for example, switch controller,
protection functions, autorecloser function, or a 61850 client residing in another IED or the
operator place. SXSWI executes commands, evaluates block conditions and evaluates different
Section 14 1MRK 502 066-UUS B
Control