14.3.9.3 Signals
PID-6712-INPUTSIGNALS v3
Table 497: XLNPROXY Input signals
Name Type Default Description
BEH INTEGER -1 Behaviour
BEH_VLD BOOLEAN 0 Valid data on BEH input
LOC BOOLEAN 0 Local control behaviour
LOC_VLD BOOLEAN 0 Valid data on LOC input
BLKOPN BOOLEAN 0 Block opening
BLKOPN_VLD BOOLEAN 0 Valid data on BLKOPN input
BLKCLS BOOLEAN 0 Block closing
BLKCLS_VLD BOOLEAN 0 Valid data on BLKCLS input
POSVAL INTEGER 0 Switch position, Pos.stVal
POSVAL_VLD BOOLEAN 0 Valid data on POSVAL input
OPCNT INTEGER -1 Operation counter
OPCNT_VLD BOOLEAN 0 Valid data on OPCNT input
BLK BOOLEAN 0 Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN 0 Valid data on BLK input
STSELD BOOLEAN 0 The controllable data is in the status "selected”
STSELD_VLD BOOLEAN 0 Valid data on STSELD input
OPRCVD BOOLEAN 0 Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN 0 Valid data on OPRCVD input
OPOK BOOLEAN 0 Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN 0 Valid data on OPOK input
EEHEALTH INTEGER -1 External equipment health
EEHEALTH_VLD BOOLEAN 0 Valid data on EEHEALTH input
OPCAP INTEGER -1 Operating capability
OPCAP_VLD BOOLEAN 0 Valid data on OPCAP input
COMMVALID BOOLEAN 0 Communication valid
XIN GROUP
SIGNAL
- Execution information from CSWI
PID-6712-OUTPUTSIGNALS v3
Table 498: XLNPROXY Output signals
Name
Type Description
XPOS GROUP SIGNAL Group connection to CSWI
SELECTED BOOLEAN Select conditions are fulfilled
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
OPENPOS BOOLEAN Apparatus open position
Table continues on next page
1MRK 502 066-UUS B Section 14
Control
857
Technical manual