14.3.10.3 Signals
PID-3561-INPUTSIGNALS v4
Table 501: QCRSV Input signals
Name Type Default Description
EXCH_IN INTEGER 0 Used for exchange signals between different BayRes blocks
RES_RQ1 BOOLEAN 0 Signal for apparatus 1 that requests to do a reservation
RES_RQ2 BOOLEAN 0 Signal for apparatus 2 that requests to do a reservation
RES_RQ3 BOOLEAN 0 Signal for apparatus 3 that requests to do a reservation
RES_RQ4 BOOLEAN 0 Signal for apparatus 4 that requests to do a reservation
RES_RQ5 BOOLEAN 0 Signal for apparatus 5 that requests to do a reservation
RES_RQ6 BOOLEAN 0 Signal for apparatus 6 that requests to do a reservation
RES_RQ7 BOOLEAN 0 Signal for apparatus 7 that requests to do a reservation
RES_RQ8 BOOLEAN 0 Signal for apparatus 8 that requests to do a reservation
BLOCK BOOLEAN 0 Reservation is not possible and the output signals are reset
OVERRIDE BOOLEAN 0 Signal to override the reservation
RES_DATA INTEGER 0 Reservation data coming from function block ResIn
PID-3561-OUTPUTSIGNALS v4
Table 502: QCRSV Output signals
Name Type Description
RES_GRT1 BOOLEAN Reservation is made and the apparatus 1 is allowed to operate
RES_GRT2 BOOLEAN Reservation is made and the apparatus 2 is allowed to operate
RES_GRT3 BOOLEAN Reservation is made and the apparatus 3 is allowed to operate
RES_GRT4 BOOLEAN Reservation is made and the apparatus 4 is allowed to operate
RES_GRT5 BOOLEAN Reservation is made and the apparatus 5 is allowed to operate
RES_GRT6 BOOLEAN Reservation is made and the apparatus 6 is allowed to operate
RES_GRT7 BOOLEAN Reservation is made and the apparatus 7 is allowed to operate
RES_GRT8 BOOLEAN Reservation is made and the apparatus 8 is allowed to operate
RES_BAYS BOOLEAN Request for reservation of other bays
ACK_TO_B BOOLEAN Acknowledge to other bays that this bay is reserved
RESERVED BOOLEAN Indicates that the bay is reserved
EXCH_OUT INTEGER Used for exchange signals between different BayRes blocks
1MRK 502 066-UUS B Section 14
Control
861
Technical manual