PID-6559-INPUTSIGNALS v3
Table 521: TR8ATCC (90) Input signals
Name Type Default Description
I3P1 GROUP
SIGNAL
- Input group for current on HV side
I3P2 GROUP
SIGNAL
- Input group for current on LV side
V3P2 GROUP
SIGNAL
- Input group for voltage on LV side
BLOCK BOOLEAN 0 Block of function
MANCTRL BOOLEAN 0 Binary "MAN" command
AUTOCTRL BOOLEAN 0 Binary "AUTO" command
PSTO INTEGER 0 Operator place selection
RAISEV BOOLEAN 0 Binary "UP" command
LOWERV BOOLEAN 0 Binary "DOWN" command
EAUTOBLK BOOLEAN 0 Block the voltage control in automatic control mode
DEBLKAUT BOOLEAN 0 Binary "Deblock Auto" command
LVA1 BOOLEAN 0 Activation of load voltage adjust. factor 1
LVA2 BOOLEAN 0 Activation of load voltage adjust. factor 2
LVA3 BOOLEAN 0 Activation of load voltage adjust. factor 3
LVA4 BOOLEAN 0 Activation of load voltage adjust. factor 4
LVARESET BOOLEAN 0 Reset LVA adjustment to 0
RSTERR BOOLEAN 0 Resets the automatic control commands raise and lower
DISC BOOLEAN 0 Disconnected transformer
Q1ON BOOLEAN 0 Capacitor or reactor bank 1 connected
Q2ON BOOLEAN 0 Capacitor or reactor bank 2 connected
Q3ON BOOLEAN 0 Capacitor or reactor bank 3 connected
SNGLMODE BOOLEAN 0 The voltage control in single control
T1INCLD BOOLEAN 0 Transformer1 included in parallel group
T2INCLD BOOLEAN 0 Transformer2 included in parallel group
T3INCLD BOOLEAN 0 Transformer3 included in parallel group
T4INCLD BOOLEAN 0 Transformer4 included in parallel group
T5INCLD BOOLEAN 0 Transformer5 included in parallel group
T6INCLD BOOLEAN 0 Transformer6 included in parallel group
T7INCLD BOOLEAN 0 Transformer7 included in parallel group
T8INCLD BOOLEAN 0 Transformer8 included in parallel group
FORCMAST BOOLEAN 0 Force transformer to master
RSTMAST BOOLEAN 0 Reset forced master transformer to default
ATCCIN GROUP
SIGNAL
- Group connection from YLTCOUT
HORIZ1 GROUP
SIGNAL
- Group connection for horizontal communication from T1
Table continues on next page
Section 14 1MRK 502 066-UUS B
Control
890
Technical manual