Name Values (Range) Unit Step Default Description
Averag3TimeReq No
Yes
- - No Use average of 3 time requests
PairedPoint No
Yes
- - Yes Enable paired point
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
PID-4134-SETTINGS v6
Table 574: MST1TCP Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
ValMasterAddr No
Yes
- - Yes Validate source (master) address
MasterIP-Addr 0 - 18 IP
Address
1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 IP
Address
1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit
2:BIWithStatus
- - 1:BISingleBit Object 1, default variation
Obj2DefVar 1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
- - 3:BIChWithRelTi
me
Object 2, default variation
Obj3DefVar 1:DIWithoutFlag
2:DIWithFlag
- - 1:DIWithoutFlag Object 3, default variation
Obj4DefVar 1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
- - 3:DIChWithRelTi
me
Object 4, default variation
Obj10DefVar 1:BO
2:BOStatus
- - 2:BOStatus Object 10, default variation
Obj20DefVar 1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
- - 5:BinCnt32WoutF Object 20, default variation
Table continues on next page