Section 15 Logic
15.1 Tripping logic SMPPTRC (94)
IP14576-1 v4
15.1.1 Identification
SEMOD56226-2 v6
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic SMPPTRC
I->O
SYMBOL-K V1 EN-US
94
15.1.2 Functionality
M12275-3 v10
A function block for protection tripping is always provided as basic for each circuit breaker
involved in the tripping of the fault. It provides a settable pulse prolongation to ensure a trip pulse
of sufficient length, as well as all functionality necessary for correct co-operation with
autoreclosing functions.
The trip function block also includes a settable latch functionality for evolving faults and breaker
lock-out.
15.1.3 Function block
M12638-3 v6
ANSI05000707-2-en.vsd
SMPPTRC (94)
BLOCK
BLKLKOUT
TRINP_3P
TRINP_A
TRINP_B
TRINP_C
PS_A
PS_B
PS_C
1PTRZ
1PTRGF
P3PTR
SETLKOUT
RSTLKOUT
TRIP
TR_A
TR_B
TR_C
TR1P
TR2P
TR3P
CLLKOUT
ANSI05000707 V2 EN-US
Figure 481: SMPPTRC (94) function block
1MRK 502 066-UUS B Section 15
Logic
937
Technical manual