15.1.5 Settings
PID-3556-SETTINGS v2
Table 587: SMPPTRC (94) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
Program 3 phase
1p/3p
1p/2p/3p
- - 1p/3p Three pole; single or three pole; single, two
or three pole trip
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secures 3-pole trip when phase selection
failed
Table 588: SMPPTRC (94) Group settings (advanced)
Name Values (Range) Unit Step Default Description
TripLockout Disabled
Enabled
- - Disabled If TripLockout is set to On, it will activate
output (CLLKOUT) and trip latch. If set to
Off it will activate only CLLKOUT
AutoLock Disabled
Enabled
- - Disabled If AutoLock is set to On i will activate
lockout from input (SETLKOUT) and trip, If
set to Off it will activate only from
SETLKOUT
15.1.6 Operation principle
M12255-3 v10.1.1
The duration of a trip output signal from tripping logic common 3-phase output SMPPTRC (94) is
settable (
tTripMin
). The pulse length should be long enough to secure the breaker opening.
For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input (TRINP_3P)
through which all trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a single trip
output (TRIP) for connection to one or more of the IEDs binary outputs, as well as to other
functions within the IED requiring this signal.
AND
BLOCK
TRIN
Operation Mode
=
Enabled
OR
t
tTripMin
TRIP
Program
= 3 phase
ANSI10000266-1-en.vsd
ANSI10000266 V1 EN-US
Figure 482: Simplified logic diagram for three pole trip
1MRK 502 066-UUS B Section 15
Logic
939
Technical manual