15.6.8.2 Signals
PID-3813-INPUTSIGNALS v4
Table 633: SRMEMORY Input signals
Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
PID-3813-OUTPUTSIGNALS v4
Table 634: SRMEMORY Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
15.6.8.3 Settings
PID-3813-SETTINGS v4
Table 635: SRMEMORY Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Disabled
Enabled
- - Enabled Operating mode of the memory function
15.6.8.4 Technical data
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
Table 636: Number of SRMEMORY instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
15.6.9 Settable timer function block TIMERSET
IP11022-1 v2
M11494-3 v3
The Settable timer function block (TIMERSET) timer has two outputs for the delay of the input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an
Operation
setting
Enabled
and
Disabled
that controls the operation of the timer.