15.6.9.3 Settings
PID-3815-SETTINGS v4
Table 639: TIMERSET Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
t 0.000 -
90000.000
s 0.001 0.000 Delay for settable timer n
15.6.9.4 Technical data
GUID-C6C98FE0-F559-45EE-B853-464516775417 v1
Table 640: Number of TIMERSET instances
Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms
15.6.10 Exclusive OR function block XOR
IP11018-1 v2
M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions with boolean
variables. XOR has two inputs and two outputs. One of the outputs is inverted. The output signal
OUT is 1 if the input signals are different and 0 if they are the same.
Table 641: Truth table for XOR function block
INPUT1 INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1
15.6.10.1 Function block
M11476-3 v1
IEC04000409-2-en.vsd
XOR
INPUT1
INPUT2
OUT
NOUT
IEC04000409 V2 EN-US
Figure 501: XOR function block
Section 15 1MRK 502 066-UUS B