Quick start-up guide
24
Example 1: Extended Speed Control (AC/DC communication profile)
on ACS800 Standard application
• Set “comm Format” to “Data-INT”
• Set IP address to ‘10.0.0.6’
• Set input assembly instance to ‘71’ and size to ‘2’
• Set output assembly instance to ‘21’ and size to ‘2’
• Set configuration instance to ‘1’ and size to ‘0’
Figure 4. RSlogix 5000: Setting up the Generic Ethernet Module
to use Extended Speed Control assembly