Quick start-up guide
27
Table 7. Drive configuration for User Specific Control
Drive parameter Example setting for ACS550
10.01 EXT1 COMMANDS COMM
10.03 DIRECTION REQUEST
11.03 REF1 SELECT COMM
16.04 FAULT RESET SEL COMM
98.02 COMM PROT SEL EXT FBA
51.01 MODULE TYPE ETHERNET
51.02 COMM RATE 0 (Auto-negotiation)
51.03 DHCP 1 (Enabled)
51.04 - 51.07 IP ADDRESS 10.0.0.6
51.08 - 51.11 SUBNET MASK 255.255.255.0
51.12 - 51.15 GW ADDRESS 0.0.0.0
51.16 PROTOCOL 2 (ABB Drives profile)
51.19 OUTPUT 1 1 (Command word)
51.20 OUTPUT 2 2 (Reference 1)
51.23 INPUT 1 4 (Status word)
51.24 INPUT 2 5 (Actual value 1)
51.25 INPUT 3 104 (Par. 1.04 CURRENT)