Quick start-up guide
26
Example 2: User Specific Control (ABB Drives communication profile)
on ACS550
• Set “comm Format” to “Data-INT”
• Set IP address to ‘10.0.0.6’
• Set input instance to ‘103’ and size to ‘3’
• Set output instance to ‘102’ and size to ‘2’
• Set configuration instance to ‘1’ and size to ‘0’
Figure 6. RSlogix 5000: Setting up the Generic Ethernet Module
to use User Specific Control assembly