Quick start-up guide
25
Table 2. ACS800 parameter settings with PPO 6
Drive parameter Example setting for ACS800
10.01 EXT1 STRT/STP/DIR COMM.CW
10.03 REF DIRECTION REQUEST
11.03 EXT1 REF1 SELECT COMM.REF
16.04 FAULT RESET SEL COMM.CW
98.02 COMM. MODULE LINK FIELDBUS
98.07 COMM PROFILE ABB DRIVES
51.01 MODULE TYPE PROFINET IO
51.02 COMM RATE 0 (Auto-negotiation)
51.03 DHCP 0 (Disabled)
51.04 - 51.07 IP ADDRESS 10.0.0.6
51.08 - 51.11 SUBNET MASK 255.255.255.0
51.12 - 51.15 GW ADDRESS 0.0.0.0
51.16 PROTOCOL 1 (PROFINET IO)
51.18 OUTPUT 1 4001 (Gain for PID)
51.19 OUTPUT 2 2202 (Accel time 1)
51.20 OUTPUT 3 2203 (Decel time 1)
51.21 OUTPUT 4 3401 (Process variable)
51.22 INPUT 1 103 (Frequency)
51.23 INPUT 2 104 (Current)
51.24 INPUT 3 106 (Power)
51.24 INPUT 4 107 (DC bus voltage)
51.26 In/out 1-4 src 2 Disabled (Source of the
parameters selected on the PLC
side)