Drive configuration
39
*Outputs from 4 to 10 are defined separately in the PLC.
The contents are defined by a decimal number in the range of
0 to 65535 as follows:
22 Input 1
23 Input 2
24 Input 3
25 Input 4
When Modbus/TCP protocol is in use, these parameters define
the input (from drive to master) data words or drive parameters
Output PZD
Output 1 PZD3
Output 2 PZD4
……
Output 8* PZD10
0 Not used
1…99 Data set area of the drive
1
Data set 1 word 1
2
Data set 1 word 2
3
Data set 1 word 3
4
Data set 2 word 1
5
Data set 2 word 2
• • • • • •
99
Data set 33 word 3
101…9999 Parameter area of the drive
Format: (x)xyy, where (x)x = actual
signal group or parameter group; yy
= actual signal or parameter index.
E.g. 103 = actual signal 01.03; 2202
= parameter 22.02.
10000…65535 Not supported by the drive