that are updated more frequently. Reading from the Modbus/TCP
register corresponding to the parameter is faster.
When PROFINET IO protocol is in use, these parameters define
the input (from drive to master) data words or drive parameters
that can be used with the vendor specific PPO’s or in addition to
the Standard telegram 1 (see chapter Communication). Input
words correspond to PZD's according to the table below.
*Inputs from 4 to 10 are defined separately in the PLC.
The contents are defined by a decimal number in the range of
0 to 65535 as follows:
Input PZD
Input 1 PZD3
Input 2 PZD4
……
Input 8* PZD10
0 Not used
1…99 Data set area of the drive
1
Data set 1 word 1
2
Data set 1 word 2
3
Data set 1 word 3
4
Data set 2 word 1
5
Data set 2 word 2
• • • • • •
99
Data set 33 word 3
101…9999 Parameter area of the drive
Format: (x)xyy, where (x)x = actual
signal group or parameter group; yy
= actual signal or parameter index.
E.g. 103 = actual signal 01.03; 2202
= parameter 22.02.
10000…65535 Not supported by the drive