56
7 RESET 0 1 Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBIT.
Note: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0 (Continue normal operation)
8 INCHING_1 Inching 1. (Not supported by all drive types)
9 INCHING_2 Inching 2. (Not supported by all drive types)
10 REMOTE_
CMD
1 Fieldbus control enabled.
0 Control Word <> 0 or Reference <> 0: Retain last Control
Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control
enabled.
11
to
15
Drive specific
Bit Name Value Proceed to STATE/Description