Communication profiles
57
Table 6. The Status Word for the PROFIdrive communication
profile. The upper case boldface text refers to the states shown in
Figure 11.
Bit Name Value STATE/Description
0 RDY_ON 1 READY TO SWITCH ON.
0 NOT READY TO SWITCH ON.
1 RDY_RUN 1 READY TO OPERATE.
0 OFF1 ACTIVE.
2 RDY_REF 1 ENABLE OPERATION.
0 DISABLE OPERATION.
3 TRIPPED 1 FAULT.
0 No fault.
4 OFF_2_STA 1 OFF2 inactive.
0 OFF2 ACTIVE.
5 OFF_3_STA 1 OFF3 inactive.
0 OFF3 ACTIVE.
6 SWC_ON_INHIB 1 SWITCH-ON INHIBIT ACTIVE.
0 SWITCH-ON INHIBIT NOT ACTIVE.
7 ALARM 1 Warning/Alarm.
0 No Warning/Alarm.
8AT_SETPOINT 1 OPERATING. Actual value equals reference value
(i.e. is within tolerance limits).
0 Actual value differs from reference value
(= is outside tolerance limits).
9 REMOTE 1 Drive control location: REMOTE.
0 Drive control location: LOCAL.
10 ABOVE_LIMIT 1 Actual frequency or speed value equals or is greater
than supervision limit.
0 Actual frequency or speed value is within supervision
limit.