Communication
87
Table 20. PROFIdrive Parameter Request error codes
Error # Meaning Used at
0x00 Impermissible parameter
number
Access to unavailable parameter
0x01 Parameter value cannot be
changed
Change access to a parameter value
that cannot be changed
0x02 Low or high limit exceeded Change access with value outside the
limits
0x03 Invalid subindex Access to unavailable subindex
0x04 No array Access with subindex to non-indexed
parameter
0x05 Incorrect data type Change access with value that does
not match the data type of the
parameter
0x06 Setting not permitted (can only
be reset)
Change access with value unequal to 0
when this is not permitted
0x07 Description element cannot be
changed
Change access to a description
element that cannot be changed
0x09 No description data available Access to unavailable description
(parameter value is available)
0x0B No operation priority Change access rights without rights to
change parameters
0x0F No text array available Access to text array that is not available
(parameter value is available)
0x11 Request cannot be executed
because of operating mode
Access is temporarily not possible for
reasons that are not specified in detail
0x14 Value impermissible Change access with a value that is
within limits but is not permissible for
other long-term reasons (parameter
with defined single values)
0x15 Response too long The length of the current response
exceeds the maximum transmittable
length