ABB | SACE Emax 2
Accessories
1 - Overview
179 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Operating conditions
Ekip Synchrocheck,
Ekip Com
and
Ekip Signalling
function correctly:
• In the presence of auxiliary supply voltage
• With the circuit-breaker in the Racked-in position (if the CB version is withdrawable)
The limitations listed below apply in all the other cases:
Module\ Condi-
tion
Ekip Synchro
-
check
Ekip Com
Ekip Signalling
2K
Ekip Signalling
3T
Ekip Signalling
10K
Ekip Signalling
4K
Module power
supply absent
Synchronism
contact open
Communication:
absent
Output contacts:
open
Output contacts:
open
CB in Test
(1)(2)
position
Synchronism: not
available
(4)
Communication:
active
Inputs and output
contacts: available
Inputs and output
contacts: available
CB in
DISCONNECTED
(1)
(3)
position
Synchronism: not
available
(4)
Communication:
partially active
(5)
Inputs and output
contacts: partial
available
(6)
Module power
supply off (Output
contacts:: open)
(1)
the description refers to the module when correctly on and with the CB in the indicated position
(2)
in the Test position, the Trip unit is connected to the modules and all information is available on
the display or via external communication
(3)
in the Racked-out position, connection and communication between Trip unit and modules is
interrupted. Information is not available/valid
(4)
due to voltage not connected to the internal sockets
(5)
see System Interface, INFORMATION WITH PROTECTION TRIP UNIT DISCONNECTED section (next
page)
(6)
the outputs only function correctly if configured as: input status (of module itself) or non-
communication with Trip unit. For all other configurations, the module forces the Outputs as per
Contact Type parameter (NO, NC).
System Interface
Document 1SDH001140R0001.zip, describing how to use the Ekip Com communication modules correctly,
is available in ABB library; the file contains:
Document Description
1SDH001140R0001.pdf
Guidelines with details about how to put the communication modules
into service, with reference to the protocols and supporting documents
1SDH001140R0001.xlsx
Table with the references of all the registers for parameters, controls,
measurements, etc.
The .zip file contains the files for supplementing Ekip Touch in the available communication networks,
with the specific Ekip Com module and an IMPORTANT file with notes on how to use the files:
File
(1)(2)
Protocol / Ekip Com module
ABBS0E7F.gsd + EkiDPB.bmp
File .gsd and module image for configuring
Ekip Com
Profibus DP
Ekip_COM_EtherNetIP_M4_vx_xx.eds File .eds for configuring
Ekip Com EtherNet/IP
TM
Ekip_COM_DeviceNet_vx_xx.eds File .eds for configuring
Ekip Com DeviceNet
TM
ABBECxxxx_Ed1.icd
ABBECxxxx_Ed2.icd
File .icd for configuring
Ekip Com IEC 61850
GSDML-Vx.xx.xml File .xml for configuring
Ekip Com Profinet
(1)
The files are also valid for the respective Redundant versions.
(2)
Check the Firmware version of your module so as to choose the file with the correct configuration.