ABB | SACE Emax 2
External electronic accessories
5 - Ekip Com Modbus TCP
225 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Client/Server
Parameter for changing the configuration of the module from
Server Only to Client and Server and for integrating it into an
interactive data exchange network (see Ekip Com Hub on page
240)
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
Server only
IEEE 1588
enable
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
Master IEEE
1588
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1588 delay
mechanism
Allows the data exchange mode between module and master,
either Peer-to-Peer or End-to-End, to be selected.
End-to-End
SNTP Client
enable
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(1)
OFF
Force Static IP
Address
Allows the network server that supplies the SNTP to be set. 0.0.0.0
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving
Time
Used to select whether daylight saving time is present (ON) or
not (OFF) in the country to which the synchronization time refers
OFF
Disable
Gratuitous ARP
Permits (Enabled ARP) the periodic generation of a Gratuitous
ARP message, used by Ekip Connect to rapidly find the modules
via Ethernet scan without knowing the IP address beforehand
ARP Enabled
Access
protected by
password
Enables the writing operations performed via the network to be
protected by a password (Request password)
Standard mode
IEEE 1588
Boundary clock
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
clock by all the slaves/devices in the same local network, even
when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network)
OFF
Enable
package
Limitation
Enables the Rate limiter function, which limits the number of
packages entering the module from the network, to be activated/
deactivated
Disable
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e
result
Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server
Synchronisation
State of synchronism with SNTP server
IEEE 1588 status
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of the higher level
master