External electronic accessories
6 - Ekip Com Profinet
227 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
Power supply
Ekip Com Profinet
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 133
LED Description
Power
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (1)
Indicates the communication state:
• Off: incorrect connection, signal absent
• on fixed: correct connection
Activity (2)
Indicates the communication state:
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the
Settings
menu (page 49).
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version
Identifier and SW version of the module
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device