ABB | SACE Emax 2
Ekip Touch - Protections
3 - Voltage protections
66 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
OV Protection
Function
The protection sends a TRIP command if one or more line-to-line voltages detected by the unit exceed
threshold U9 for longer than t9.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 96)
• the graph with trip curve (page 106)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold
U9
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 1 Un to 1.5 Un in 0.001 Un steps
1,05 Un
Time t9
This is the trip time of the protection; the value is given in seconds
and can be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 83).
UV2 Protection
Function
UV2 protection functions in the same way as UV protection: the protection sends a TRIP command if one
or more line-to-line voltages detected by the unit drop below threshold U15 for longer than t15.
It is independent of UV protection, thus thresholds and functions of the two protections can be
programmed so as to take advantage of different plant solutions (example: signaling with UV and open
command with UV2 or vice versa, or both for signaling or tripping).
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 96)
• the graph with trip curve (page 105)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold
U15
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.05 Un to 1 Un in 0.001 Un steps
0,9 Un
Time t15
This is the trip time of the protection; the value is given in seconds
and can be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 83).