ABB | SACE Emax 2
Ekip Touch - Protections
3 - Voltage protections
67 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
OV2 Protection
U16
t
t16
V
OV2
Function
OV2 protection functions in the same way as OV protection: the protection sends a TRIP command if one
or more line-to-line voltages detected by the unit exceed threshold U16 for longer than t16.
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 96)
the graph with trip curve (page 106)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold
U16
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 1 Un to 1.5 Un in 0.001 Un steps
1,05 Un
Time t16
This is the trip time of the protection; the value is given in seconds
and can be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 86).
Phase sequence protection
The
Phase Sequence
protection enables an alarm to be activated when the sequence of line-to-line
voltages is not aligned with the sequence set by the user.
The required sequence can be set in the
Settings
menu and the protection activated in the
Advanced
menu (page 49 and page 47).
VU Protection
U14
t
t14
V
VU
Function
The protection trips if the line-to-line voltages read by the unit are unbalanced; the protection sends a
TRIP command if the detected unbalance exceeds threshold U14 for longer than t14.
The protection excludes itself if the maximum value of the line-to-line voltage is less than 0.3 Un
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 96)
the graph with trip curve (page 106)
Parameters
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold
U14
Establishes the unbalance value that trips the protection.
Unbalance is expressed in percentage value and is calculated in the
following way: % Unba = 100 x (Δmax U
mi
) / U
mi
in range: 2% to 90% in
1% steps.
NOTE: Δmax U
mi
: maximum deviation among the three voltages
calculated by comparing each line-to-line voltage with the mean
value; U
mi
: mean value of the line-to-line voltages
50 %
Time t14
This is the trip time of the protection; the value is given in seconds
and can be set within a range: 0.5 s to 60 s, in 0.5 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 86).