Ekip Touch - Protections
9 - Additional protections and functions
91 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Current thresholds
Function
The Current thresholds allow checks to be set along the current lines, to be associated with the
programmable contacts of the
Ekip Signalling
modules (in all versions).
Two pairs of programmable contacts are available:
Threshold 1 I1 and Threshold 2 I1, with control referring to I1
Threshold Iw1 and Threshold Iw2, with control relating to In
The thresholds can be enabled and set in the Advanced - Signaling menu (page 47).
IMPORTANT:
the current thresholds do not manage the trip, but only the signal
the function is activated if the trip unit is powered by auxiliary voltage
Parameters
Threshold Available parameters Default
Threshold 1 I1
Enable
: Activates the protection and availability of the threshold
in the menu
OFF
Threshold
: The value is given in percentage of threshold I1 and
can be set within the range: 50% I1 to 100% I1, in 1% steps.
50 % I1
Threshold 2 I1
Enable
: Activates the protection and availability of the threshold
in the menu
OFF
Threshold
: The value is given in percentage of threshold I1 and
can be set within the range: 50% I1 to 100% I1, in 1% steps.
75 % I1
Threshold Iw1
Enable
: Activates the protection and availability of the threshold
in the menu
OFF
Direction
: allows the user to choose whether to have the signal
when the current is higher (Up) or lower (Down) than the
threshold.
Down
Threshold
: The value is given as both absolute value (amperes)
and relative value (In) and can be set within the range: 0.1 In to 10
In, in 0.01 In steps
3 In
Threshold Iw2
Enable
: Activates the protection and availability of the threshold
in the menu
OFF
Direction
: allows the user to choose whether to have the signal
when the current is higher (Up) or lower (Down) than the
threshold.
Up
Threshold
: The value is given as both absolute value (amperes)
and relative value (In) and can be set within the range: 0.1 In to 10
In, in 0.01 In steps
3 In
Figure 28