130 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A Ekip Touch protection trip unit | 22 - Default parameters
Continued from the previous page
The Ekip Hi-Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter
Value
(1)
S2 Off; 2 In; 50 ms; Curve: t = k
D Off; 2 In; 200 ms
UV2 Off; 0.9 Un; 5 s
OV2 Off; 1.05 Un; 5 s
UF2 Off; 0.9 fn; 3 s
OF2 Off; 1.1 fn; 3 s
Network Analyzer Off
Harmonic calculation Off
Set A-B Off
The Ekip G Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter
Value
(1)
S(V) Off; type = step; 1 In; UI = 1 Un; Ks = 0.6; t20 = 1 s
RV Off; 0.15 Un; 15 s
RQ Off; Kq = -2; Q24 = 0.1 An
OQ Off; 1 Sn; 1 s
OP Off; 1 Sn; 1 s
UP Off; 1 Sn; 1 s
The Ekip G Hi-Touch trip units has additional protections, provided with the following default parameters:
Protection/Parameter Value
ROCOF Off; 0.6 Hz; 500 ms
S2(V) Off; type = step; 1 In; UI2 = 1 Un; Ks2 = 0.6; t21 = 1 s
RQ2 Off; Kq = -2; Kq2 = 2; Q24 = 0.1 Sn; Q25 = 0.11 Sn; Vmin = 0.5 Un; 100 s