ABB | SACE Emax 2
186 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A Electronic accessories | 4 - Ekip Synchrocheck module
Electrical characteristics
The following table lists the electrical characteristics of the module:
Component Characteristics
Input voltage 0...120 V AC rated
Input frequency 30…80 Hz
Output contact
• Maximum switching voltage
(1)
: 150 V DC / 250 V AC.
• Breaking capacity
(1)
: 2 A @ 30 V DC, 0.8 A @ 50 V DC, 0.2 A @ 150 V DC,
4A @ 250 V AC.
• Dielectric strength between open contacts: 1000 V AC (1 minute @ 50 Hz).
• Dielectric strength between each contact and coil: 1000 V AC (1 minute @
50 Hz).
(1)
Data related to a resistive load.
Isolation transformer
Between the external contacts of the circuit-breaker and the inputs of the module, an isolation transformer
must always be installed having the following characteristics:
Characteristics Description
Mechanical
• Mounting: EN 50022 DIN43880 guide.
• Material: self-extinguishing thermoplastic.
• Protection degree: IP30.
• Electrostatic protection: with shield to be connected to ground.
Electrical
• Accuracy class: 0.5.
• Performance: 5 VA.
• Overload: 20 % permanent.
• Insulation: 4 kV between inputs and outputs, 4 kV between shield and
outputs, 4 kV between shield and inputs.
• Frequency: 45…66 Hz.
NOTE: for the primary and secondary voltages of the transformer, see the configuration
parameters of the module, paragraph "Access from the display" on page 189).
Measurements
The following table lists the measurement accuracy for the module:
Quantity Range Accuracy
Voltage 10…120 V AC ± 1 %
(1)
Frequency
(2)
30…80 Hz ± 0.1 %
(3)
Phase
(4)
-180...+180 ° ± 1 °
(1)
With live busbar.
(2)
With a live busbar, the frequency measurement is available with a voltage measured 36 V AC, and is
unavailable with a voltage measured 32 V AC.
(3)
In the absence of harmonic distortion.
(4)
The phase measurement refers to the phase difference between internal and external voltage.