ABB | SACE Emax 2
48 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A Ekip Touch protection trip unit | 6 - Menu
Advanced menus
The following table shows the submenus and the protections associated to the menu Advanced, and the
relevant Ekip Touch trip units.
IMPORTANT:
• Selecting a protection opens the list of the parameters that can be set for the
selected protection.
• With Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see
the Settings menu), the protections can be set according to two configurations (Set
A and Set B), from which the default configuration can be selected.
Advanced
Trip units
Set A
(1)
Set B
(1)
S(V) Protection - - G-Touch
G Hi-Touch
S2(V) Protection - - -
MCR Protection Touch
Hi-Touch
G-Touch
D Protection - -
IU Protection
Touch
G-TouchRc Protection
(2)
UV Protection Touch
(3)
UV2 Protection - -
OV Protection Touch
(3)
G-Touch
OV2 Protection - -
RV Protection - -
G-TouchVU Protection Touch
(3)
Hi-Touch
UF Protection Touch
(3)
UF2 Protection - -
OF Protection Touch
(3)
G-Touch
OF2 Protection - -
ROCOF Protection - - -
RP Protection Touch
(3)
Hi-Touch
G-Touch
RQ ProtectioN - -
OP Protection - -
OQ Protection - -
UP Protection - -
Synchrocheck
(4)
Touch
(3)
Hi-Touch
Alarms Touch
(3)
Current thresholds
Touch
Functions
External Trip
(5)
Trip RESET
(6)
Switch On SET B
(7)
(1)
Submenus available with Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see the
Settings menu).
(2)
Protection available with Rating Plug Rc and Ekip Measuring Pro modules, and toroid Rc (see the menu
Settings, Circuit Breaker, Ground protection), and alternative to the Gext protection (see the Protections menu).
(3)
Protection available with Ekip Measuring Pro module.
(4)
Protection available with the Ekip Synchrocheck module.
(5)
It opens a list of the parameters that can be set for programming the opening of the circuit-breaker.
(6)
It opens a list of the parameters that can be set for programming the reset of the tripping signal.
(7)
It opens a list of the parameters that can be set for programming the switching of the protection configuration
from A to B.

Table of Contents

Other manuals for ABB SACE Emax E4.2

Related product manuals