EasyManuals Logo

ACL CSC400 User Manual

ACL CSC400
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
60
Appendix D - Troubleshooting
Burner Management Troubleshooting
#
Issue
Possible Reason
Corrective Action
1
Fails to attempt ignition
Blown fuse
Check if the display is on or not: a menu screen or the
Status screen should always be displayed.
If Display is off, replace fuse with a 6.3A max fuse
Supply voltage too low
Ensure that the minimum input voltage is 11.5VDC
(measured with a volt meter) for use with 2-3
solenoid outputs
Poor power connections
Check all connections on the terminal strips. Ensure
that there are no short circuits, that the wires are
tightly gripped inside the terminals, and that the
screws on each terminal are tight.
POC terminal not closed, display
showing "POC"
Ensure that 12VDC is measured on both the POC+
and POC- terminals
2
Attempts ignition but
pilot doesn't light
Fuel gas supply to Pilot may be
too high or too low
Pilot fuel gas supply should be set at 5 pounds
Gap setting on ignitor/flame rod
not correct
Gap should be approximately 1/8" (3.175mm) and rod
tip needs to be cut to a sharp point
Ignition cable defective or
insulation worn
Check continuity through the ignition cable.
Multimeter should read close to zero ohms. If not,
cable needs to be replaced.
Poor ground connection
Ensure that good, thick ground connections are made
at the CSC400 and at the Pilot/burner valve.
Pilot solenoid failure
Check supplied power to solenoid. Check gas flow
through solenoid.
Plugged orifice on Pilot
Clean out Pilot orifice (Do Not redrill!)
3
Weak or Erratic Spark
Gap setting too wide or rod not
cut to a point
Shorten gap setting to approximately 1/8" (3.175mm)
and recut the ignitor rod tip.
Ignition cable defective or
insulation worn
Check continuity through the ignition cable.
Multimeter should read close to zero ohms. If not,
cable needs to be replaced.
Poor ground connection
Ensure that good, thick ground connections are made
at the CSC400 and at the ignitor tip.
Contaminated ignitor rod or Pilot
nozzle
Remove Pilot assembly, clean rod and nozzle, and
reinstall.
4
Solenoid valve not
opening
No power to solenoid valve or
faulty solenoid valve
Replace defective solenoid valve
5
Solenoid valve opens but
then closes again
(intermittent operation)
Wrong Low Power Solenoid
Driver setting for the attached
solenoids
Verify that the Low Power Solenoid Driver DIP
switch settings are matched to the solenoid valves
connected to the CSC400.
Voltage droop on input
Some larger solenoid valves rated for 12VDC require
an output voltage very near to 12VDC. Measure the
output voltage on the solenoid terminals to ensure that
it's sufficient (approx. >= 11.5VDC).
Higher current drawn on each solenoid output will
cause slightly higher voltage drops which may
interfere with solenoid operation. Input voltage may

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ACL CSC400 and is the answer not in the manual?

ACL CSC400 Specifications

General IconGeneral
BrandACL
ModelCSC400
CategoryController
LanguageEnglish