32
Top Menu Options
The CSC400 Top Menu allows users to select a variety of submenus with additional options and configurations available. It
provides the most often used options at the top of the menu list.
Change lines displayed on Top Screen
Change Temperature Setpoints and Deadband values
Show the most recent shutdowns for IGN1 & 2
View/Reset TMain1 Solenoid ON Time
View/Reset TMain2 Solenoid ON Time
Change Solenoid Driver Cycle Times
Set the time in the CSC400
Set the date in the CSC400
Change Modbus Comm. Settings
Shows firmware version, diagnostics information
Reset (clear) Shutdown Log
Reset (clear) Temperature Logs
Reset Settings to default
Recalibrate Thermocouple inputs
Configuration Menu Options
The CSC400 provides the options most often changed in the first menu named the "Configuration" menu. This menu allows
users to set the operation mode, which ignitors and thermocouples are enabled, intermittent or continuous mode, deadband
values, 4-20mA output and input modes, and shutdown latch settings.
Configuration Menu
Selections
Ignitor 1 Enabled/Disabled
Ignitor 2 Enabled/Disabled
Use TC3 as an auxiliary High-temp SD
Enable Low Temp Shutdown/Alarm on
Thermocouples?
- Either SD or Alarm can be selected for
any combination of thermocouples.
- There is only one Low Temp setpoint for
all three thermocouples.
(SD TC1, TC2, TC3, TC1&2,
TC1&3, TC2&3, TC1&2&3),
(ALM TC1, TC2, TC3, TC1&2,
TC1&3, TC2&3, TC1&2&3)
Intermittent / Continuous Pilot Select
Intermittent / Continuous Pilot
Pilot On to Mains On Delay
Main(s) On to TMain(s) On Delay
Select Number of trials for ignition before
Flame Fail lock-out
Shutdown both Ignitor outputs upon Flame
Fail on one Ignitor? Yes/No
Alarm Only if Both Ignitors are in Flame
Fail: "ALM Only if Both FF"
or Alarm if Any Ignitor goes into Flame
Fail: "ALM if Any IGN FF"
Both Ignitors must be enabled for this to
have an effect on the Alarm/Status contacts
"ALM if Any IGN FF"