Installation and Operations Manual
for the
CSC400 Combustion
Safety Controller
(Rev 1D)
WARNING
This manual must be read in its entirety before installation of this controller.
Installation must be performed by a qualified technician and must adhere to
the standards set by the local regulatory authorities.
ACL is not responsible for the misuse or incorrect application of this product.
V 2.21

Table of Contents

Questions and Answers

  • R
    Rebecca MorganAug 3, 2025
    Why ACL CSC400 fails to attempt ignition?
    • D
      Dr. Autumn Archer MDAug 3, 2025
      The ACL Controller might fail to attempt ignition due to several reasons: * A blown fuse: Check if the display is on. If it's off, replace the fuse with a 6.3A max fuse. * Low supply voltage: Ensure the input voltage is at least 11.5VDC when measured with a voltmeter. * Poor power connections: Inspect all connections on the terminal strips for short circuits and ensure wires are tightly secured and screws are tight. * POC terminal not closed: Verify that 12VDC is measured on both the POC+ and POC- terminals.
  • D
    david14Aug 23, 2025
    How to fix a weak or erratic spark on ACL CSC400 Controller?
    • L
      Lisa BassAug 23, 2025
      A weak or erratic spark on the ACL Controller can be caused by: * Incorrect gap setting: The gap setting may be too wide, or the rod isn't cut to a point. Shorten the gap to approximately 1/8" (3.175mm) and recut the ignitor rod tip. * Defective ignition cable: Check the ignition cable's continuity. The multimeter should read close to zero ohms; replace the cable if it doesn't. * Poor ground connection: Ensure good, thick ground connections are made at the CSC400 and at the ignitor tip. * Contaminated ignitor rod or pilot nozzle: Remove the pilot assembly, clean the rod and nozzle, and reinstall.
  • A
    angelalloydNov 10, 2025
    What to do if the ACL CSC400 attempts ignition but the pilot doesn't light?
    • M
      Misty SchwartzNov 10, 2025
      If the ACL Controller attempts ignition but the pilot doesn't light, consider the following possible causes: * Incorrect fuel gas supply: The pilot fuel gas supply may be too high or too low. It should be set at 5 pounds. * Incorrect gap setting: The gap setting on the ignitor/flame rod might not be correct. It should be approximately 1/8" (3.175mm), and the rod tip needs to be cut to a sharp point. * Defective ignition cable: Check the continuity through the ignition cable; it should read close to zero ohms. Replace the cable if it doesn't. * Poor ground connection: Ensure good, thick ground connections are made at the CSC400 and at the Pilot/burner valve. * Pilot solenoid failure: Check the supplied power to the solenoid and the gas flow through it. * Plugged pilot orifice: ...

Summary

CSC400 Controller Features

Key Features List

List of CSC400 controller's features and capabilities.

CSC400 Quickstart Installation

CSC400 Input and Control Connections

CSC400 Shutdown Inputs

Gas, Level, and Auxiliary Shutdown Configuration

Config and wiring for High Gas, Low Gas, Level, Auxiliary shutdowns.

CSC400 Relay and Ignition Module Outputs

Ignition Module Wiring

Wiring for CSC400 Ignition Module 1 and 2 inputs and outputs.

Solenoid Output Connections

Wiring for Ignitor 1/2 solenoid outputs (Pilot, Main, T/Main).

CSC400 Front Panel Interface and Configuration

Adjusting Temperature Setpoints

Procedure for adjusting temperature setpoints and deadbands.

CSC400 Wiring Diagrams

FI Flame Ionization (Remote IGN)

Wiring diagram for Flame Ionization mode with remote IGN.

FI Flame Ionization (Local IGN)

Wiring diagram for Flame Ionization mode with local IGN.

4-20 mA Controlled Valve Wiring

Wiring for 4-20mA control of throttling valve.

CSC400 Controller Menu System

Configuration Menu Options

Options for configuring burner, thermocouples, and shutdown settings.

CSC400 Modbus Communications

RS-485 Cabling and Topology

RS-485 cabling details: signal naming, topology, termination.

CSC400 Shutdown Display Codes

CSC400 4-20 mA I;O Notes and DIP Switches

CSC400 Appendices

Appendix D: Troubleshooting

Troubleshooting guide for burner management and Modbus issues.