EasyManua.ls Logo

Advanced Control C220 Series - Page 40

Default Icon
225 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mechanical and Electrical Installation
C220/C420 Mechanical and Electrical Installation
39
be caused due to the influence of the distributed capacitance, thus damaging the
motor insulation or produce large leakage current to trigger inverter over current
protection. When the length of the motor cable is longer than 100 meters, AC output
reactor shall be installed.
e) Grounding terminal
:
The terminal must be grounded reliably, and the resistance of the ground wire must
be less than 0.1Ω. Otherwise, fault may be caused, or the inverter may be damaged.
Do not share the grounding terminal
and terminal N of zero line of the power
supply.
3.2.5 Control Terminals and Wiring
3.2.5.1 The terminals of the control circuit are arranged as shown in the
following diagram:
AI1
AI2
GND Y1COM
24V
COM
10V
AO1
485+ 485- DI1
DI2
DI3 DI4
GND
TB
TA
TC
Fig.3-5 Terminal Layout of the Control Circuit
3.2.5.2 Function Description of Control Terminal
Tab.3-3 Function Description of C220/C420 Inverter Control Terminal

Table of Contents