Parameter Description
C220/C420G General Flux Vector Control Inverter User Manual
69
getting start, which suits for the applications where reverse rotation is likely to occur
when small loads are getting start
1: Speed tracking restart
First of all, the inverter makes an estimate of motor speed and direction, then starts
at the frequency in accordance with the tracked motor speed. the rotating motor is
running smoothly without surge.
It is suitable for the restart upon transient power failure of large loads.
F1-01
Start model
factory default
value
0
setup
range
0
beginning from stop frequency
1
beginning from zero speed
3
beginning from maximum frequency
to complete the speed tracking process within the shortest time ,and then to select
the mode of inverter tracking motor speed.
0: to track from the frequency on power failure, generally, it selects this mode.
1: this mode is used to track from zero frequency and restart after a long period of
power supply off .
2: This mode is used to track from the maximum frequency, and is suitable for the
general power generating loads.
F1-02
Speed tracking
maximum
current
factory default value 100%
setup range
30%
180%
F1-03
Speed tracking
Fastness and
slowness
factory default value 20