Parameter Description
C220/C420G General Flux Vector Control Inverter User Manual
70
setup range
1
100
In speed tracking restart’s mode, to select its fastness and slowness. the higher this
parameter value is ,the faster the tracking speed is ,but too high value may result in
reliable tracking.
F1-04
Start up
frequency
factory
default
value
0.00Hz
setup range
0.00Hz
10.00Hz
F1-05
Start frequency
retention time
factory
default
value
0.0s
setup range
0.0s
36.0s
F1-06
DC break
current at start
factory
default value
0%
setup range
0%
100%
F1-07
DC break time
at
start
factory
default value
0.0s
setup range
0.0s
36.0s
DC break at start is used when the motor is getting to restart after stopping
completely
If the start mode is the direct start, the inverter firstly performs DC break in
accordance with the DC brake current at start, and then starts running after setting to
DC brake time at start. if it is set to 0,the inverter directly starts without passing
through the DC brake.