Parameter Description
C220/C420G General Flux Vector Control Inverter User Manual
73
current at stop
value
setup range
0%
100%
F1-17
DC brake time at
stop
factory default
value
0.0s
setup range
0.0s
36.0s
DC brake beginning frequency at stop: In the process of the deceleration stop, when
it reaches this frequency, the DC brake stop begins
DC brake current at stop: it refers to the additive DC brake quantity. The higher this
value is, the better the DC brake effect is.
DC brake time at stop: it refers to the additive time of DC brake quantity.when this
value is zero, it shows there is no DC brake process, and the inverter will stop
according to the given deceleration stop
F1-18
Brake use ration
factory default
value
100%
setup range
0%
100%
It is enabled for the inverter with built-in unit, and used to adjust the brake effect of
the bake unit
F1-19
Power
interruption
restart
factory default
value
0
setup range
0
inactive
1
Start from stop frequency
2
Start from minimum frequency
3
direct start
F1-20
Permissible time
factory default
1.0s