Caution: Prior to tuning ,it must set the correct motor rated parameters (F4-01~
F4-06)
0: None, that is ,No-Tuning
1: Static tuning ,it is suitable for this occasion that on which motor and load is hard
to take off so as to not get the rotary tuning
Operation description: setting this function code to 1 and then pressing the RUN key
with confirmation, the inverter will operate static tuning
2: complete tuning
To ensure the dynamic control performance on the inverter, please select the rotary
tuning, the motor must be disconnected with the loads (i.e. no-load)in the process of
the rotary tuning.
Upon selection of rotary tuning, the inverter will conduct static tuning at first. at the
end of static tuning ,the motor will accelerate to 80% of the rated motor frequency in
accordance with the setup acceleration time of F4-12 and maintain for a period of
time. Then the motor will decelerate to zero speed in accordance with the setup
acceleration time of F4-13,by this time the rotary tuning is finished.
Operation description:setting this function code to 2 and pressing RUN key with
confirmation ,then the inverter will operate rotary tuning
tuning operation description
When F4-00 is set to 1or 2 ,press ENTER key ,’TUNE will be displayed and flashed,
then press RUN key to operate parameter tuning, at this time the displayed TUNE