3.9.5 View - Inputs
This function shows the current operational condition for all Zones and Individual Inputs. The display
presents a list of all of the zones containing input devices, with the first zone highlighted. For example:
[Inputs] More>
Zone Mode Location
0001 Enabled Kitchen
0002 Disabled Reception
0013 Enabled Lobby
0014 Enabled Corridor
Press the ÏÐ buttons to highlight the required zone and then press the Î button to view the
individual inputs. For example:
[ Inputs in Zone 0001] <More>
Mld Mode Device text
/ 1 Enabled Kitchen
/ 2 Disabled Reception
3.9.6 View - Outputs
This function shows the current operational condition for all Outputs.
[Outputs] More>
Zone Location
0002 Reception
0003 Ground Floor
0013 First Floor Corridor
0014 First Floor
Press the ÏÐ buttons to highlight the required zone and then press the Î button to view the
individual outputs. For example:
[ Outputs in Zone 0003] <More>
Mld Mode Device text
Enabled Kitchen
Disabled Reception
Press the Î button to view further information on each point, for example:
[ Outputs in Zone 0003] <More>
Mld Mode State Type
Enabled Off SOUNDER
Disabled RELAY
A * symbol preceding the state (e.g. *On) indicates the device has been configured as an inverted
output (e.g. a fault relay that is designed to de-energise when a fault occurs).
The state of an output that is disabled is not shown, as it will inherently be in the off condition.