EasyManua.ls Logo

Aerco BENCHMARK 6000 - Page 56

Aerco BENCHMARK 6000
210 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 3 OPERATION
Page 56 of 210 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0086_0D
03/20/14 Ph.: 800-526-0288 GF-133
Table 3-9: Gas Pressure De-Rating Chart
Gas Pressure @
SSOV (inches W.C.)
Energy Input
(BTU/hr)
Oxygen
(%O2)
DeRating
(% Full Fire)
Inlet
Outlet
56
8
6,000,000
5.40
0%
14
8
6,000,000
5.40
0%
13
8
5,860,000
5.45
2%
12
7.95
5,860,000
5.41
2%
11.5
7.5
5,740,000
5.77
4%
11
7.1
5,610,000
6.17
6%
Figure 3-8: Relationship Between Air/Fuel Valve Position and Energy Input

Table of Contents